Application

Approval Letter View

Approved No :- DGMS APPROVAL NO.- 661 of 2013

NO: E-29021|30479|2020|Electrical(HQ)                                                                                                                                                            Dhanbad, Date: 31.07.2020

DGMS APPROVAL NO.- 661 of 2013

From

Director General of Mines Safety (Officiating)
Directorate General of Mines Safety,
P.O & Distt: Dhanbad - 826 016.

To

NANDINI CHAKRAVARTY, Mine Line Pvt. Ltd., 23, INDRANI PARK
West Bengal, KOLKATA, KOLKATA, 700033

Sub:    DGMS approval No. 661 of 2013 under Regulation 208 (3) of the Coal Mines Regulations, 2017 for Flameproof machine distributor in fabricated MS construction, designated by type No. MD-1 manufactured by M/s. Mine Line Pvt. Ltd., Kolkata conforming to IS/IEC 60079-0:2004 and IS/IEC 60079-1:2007 for use in belowground Coal Mines– Renewal thereof.

Ref:    CIMFR test report No. CIMFR/TC/P/H735 dated 07.02.2013.

                                                                                                                                              IDENTIFICATION MARK

DGMS APPROVAL NO. 661 OF 2013

Dear Madam,

Please refer to your online letter No. E-29021/30479/2020/Electrical (HQ) and letter No. M20/DGMS/16 dated 12.03.2020 on the above subject.

Based on DGMS approval no. 661 of 2013 issued by this Directorate’s letter no. 333/886/EHQ dated 03.05.2013, BIS Licence no. CM/L-0893166 and above test report under reference and on the basis of extension of validity of IS/IEC60079-1:2007 standard and implementation of revised IS/IEC 60079-1:2014 test standard up to 23rd october 2020 notified by BIS reference CMD-III General, dated 27.03.2020,, I hereby renew the approval upto 23.10.2020  for use in belowground Coal Mines, subject to compliance with conditions stipulated in the original approval as well as annexure enclosed with this renewal letter.

Please note that application for renewal, if required by you should be made  before the date of expiry of the approval.

Your Faithfully,
(DINESH KUMAR SAHU)
Director General of Mine Safety - (Officiating)
Date : 31/07/2020

Enclosure: Annexure

                                  

Annexure

          Conditions for renewal DGMS approval No. 661 of 2013 under Regulation 208 (3) of the Coal Mines Regulations, 2017 for Flameproof machine distributor in fabricated MS construction, designated by type No. MD-1 manufactured by M/S Mine Line Pvt. Ltd., Kolkata conforming to IS/IEC 60079-0:2004 and IS/IEC 60079-1:2007 for use in belowground Coal Mines.

  1. (i) Every unit shall carry conspicuously in a permanent manner the aforesaid  

      identification mark, i.e. ‘DGMS APPROVAL NO.  661  of 2013.”.

     In addition, every unit shall also carry permanently this Directorate’s approval mark as given below :

                                                                                                                    

  (ii) In the nameplate marking shall be in accordance with the applicable requirements of the relevant standards.

2.       (a)The design of the electrical circuit shall not be changed without obtaining prior approval from this Directorate.

          (b)Conspicuous warning inscriptions against opening the cover of the main enclosure or of any apparatus which gives access to the flameproof enclosures on live parts or which is designed to receive                    cable  attachment unless the supply to the unit is isolated at source, shall be affixed permanently on the respective part to ensure that all live parts within the unit are made dead and safe.

           3.       Spare parts shall be made readily available to the user as and when required for proper maintenance of the equipment.

           4.       (a) The customer shall be supplied the copy of this approval letter, the test report from the testing laboratory with the lab certified drawing , an extract of the condition & special conditions,                                      maintenance  schedule, if any, recommended by the testing laboratory in their test report(s) so as to maintain safety features of apparatus/equipment.

                   (b) The customer shall also be provided a copy of factory test report along with drawings, instruction manual on the installation, operation and maintenance of the equipment and spares parts                            catalogue at the time of delivery of the equipment.

           5.       The user shall furnish the performance report of the equipment directly to this Directorate after one (01) year of actual use.

            6.         While seeking Renewal of Approval, valid BIS license in the case of Indian manufacturers and in case of foreign manufacturers, QAR/QAN, as may be applicable shall be submitted and the same                 shall remain  valid as long as the apparatus is manufactured and marketed.

           7.       Any modification to the equipment that might be considered necessary at a later date shall be effected upon being so directed by this Directorate.

             8.       An officer of this Directorate may at any time draw a sample either from the factory or from the user and get it tested at the cost of the manufacturer.  If the test reports are not satisfactory, this                        approval shall  be deemed to be suspended.

9.       If there occurs any revision of standards applicable to the product/equipment , the manufacturer shall get the product/equipment tested as per revised standards and submit test reports to the  customer  for information and to this  Directorate for further approval/renewal.

10.     The approval of the subject equipment is with regard to Ex standards mentioned herein.  Other relevant standards applicable for assessment of its electrical parameters required under type test have not been taken into consideration.

11.     All circulars/general approvals issued by DGMS from time to time, relevant to the equipment shall also be complied with.

12.     The plug and socket assembly affixed to the motors/panel, will be so interlocked as to prevent removal of plug from the socket while alive.

13.     The relevant provisions of the Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2010 shall be complied with in all matter relating to the installation, operation and maintenance of the equipment.

14.     The approval is renewnal  upto 23.10.2020.

15.     The equipment manufactured subsequently shall be identical to the proto type tested at CIMFR vide test report No. CIMFR/TC/P/H735 dated 07.02.2013.

16.     At the time of applying for renewal, details of supply with name of mines, purchase order and date shall be furnished with the application.

17.     If at any time any of the conditions subject to which this approval has been granted, is violated or not complied with, this approval shall be deemed to have been revoked with immediate effect.

18.     The above approval may be amended or withdrawn at any time, if considered so necessary in the interest of safety and is being issued without prejudice to any other provisions of law which may be or may become applicable at any time.

 

 
(DINESH KUMAR SAHU)
Director General of Mine Safety - (Officiating)
Date : 31/07/2020
THIS IS A SYSTEM GENERATED DOCUMENT, DOES NOT REQUIRE ANY SIGNATURE.